Thermo-Chillers (Circulating Fluid Temperature Controllers) Dual Channel Thermo chiller for Lasers
Thermo-chiller Compact Dual/Basic Type for Lasers HRLE
-
・The temperatures of 2 fluid channel systems can be controlled individually by 1 chiller.
・Space saving, Reduced wiring
Footprint reduced by 21%
One power supply system for 2 channels
・Energy saving
Power consumption reduced by 17%
Series | Set temperature range |
Cooling capacity (CH1, 2 total) |
Temperature stability |
Cooling method | Circulating fluid |
---|---|---|---|---|---|
HRLE050-A | CH1:15 to 25℃ CH2:CH1 temperature + 0 to 15℃ |
4.8kW/5.8k (50Hz/60Hz) |
CH1:±0.1 CH2:±0.5 |
Air-cooled refrigeration |
Tap water, Deionized (pure) water |
HRLE050-W | CH1:15 to 25℃ CH2:CH1 temperature + 0 to 15℃ |
4.8kW/5.8k (50Hz/60Hz) |
CH1:±0.1 CH2:±0.5 |
Water-cooled refrigeration |
Tap water, Deionized (pure) water |
HRLE090-A | CH1:15 to 25℃ CH2:CH1 temperature + 0 to 15℃ |
8.0 kW/9.5 kW (50 Hz/60 Hz) |
CH1: ±0.1 CH2: ±0.5 |
Air-cooled refrigeration |
Tap water, Deionized (pure) water |
HRLE090-W | CH1: 9 kw,19 kW, 26 kW CH2: 1.0 kW (Max. 1.5 kW) |
9.5 kW/11.0 kW (50 Hz/60 Hz) |
CH1: ±0.1 CH2: ±0.5 |
Water-cooled refrigeration |
Tap water, Deionized (pure) water |
Features
With functions narrowed down, 2 independent temperature control systems have been achieved with only a single compressor, a single pump, and a single tank.
Space saving: Footprint reduced by 21%
Energy saving Power consumption reduced by 17%
Space saving
The temperatures of 2 fluid channel systems can be controlled individually. Compact
Reduced wiring/labor
One power supply system for temperature control of 2 channels, Less work-hour for wiring
Energy saving
Variations
One compressor controls 2 channels.
Temperature stability: ±0.1°C (CH1) When a load is stable
By controlling the inverter fan and electronic expansion valve simultaneously, it maintains the good temperature stability when the heat load fluctuates.
-
Electric conductivity control set
(With DI filter + Solenoid valve kit for control)
-
Particle filter set
Protection of the electrical unit: IPX4
Circulating fluid can be heated without a heater.
Globally compatible power supplies (Europe, Asia, Oceania, Central and South America)
Toolless inspection and cleaning of air-cooled condenser
∗ For air-cooled refrigeration
Increased cooling capacity function (Option) ∗ HRLE090 only
The inverter for compressor increases the cooling capacity of the 50 Hz area to that of the 60 Hz area.
Convenient functions
Self-diagnosis function and check display
Communication functions
Serial communication (RS485) and contact I/Os (2 inputs and 3 outputs) are equipped as standard.
This allows for communication with the customer equipment and system construction, depending on the application.
A 24 VDC output can be also provided and is available for use with flow switches (SMC’s PF3W, etc.).