|Static Neutralization Equipment
-
-
If the MAIN or ION/HV LED is blinking red on an IZS40 or the MAIN, ION/HV, NDL, RC, or SNSR LED is blinking red on an IZS41/42, the CPU is malfunctioning due to noise, etc. Possible countermeasures include ① keeping the ionizer away from the noise source, ② separating wiring if the power line and ionizer are wired together, and ③ installing a noise filter in the ionizer power supply. In order to clear the alarm, remedy the cause of the error, and then turn the power ON again.